3x36GTSIS1.630MC-WSK-L2-MC

Description

Description

Standards

  • Test
    CENELEC HD 629.2

Application

GTSIS1 heat-shrink shield break straight joints are designed for unarmored, plastic insulated cables with Cu wire or Cu/Al tape screen, to accommodate either crimped or mechanical connectors.

Nexans GTSIS provide screen interruption in the joint in order to separate earthing system networks.

It can be supplied with single (GTSIS “L”) or double (GTSIS “L2”) earthing exits to allow screen transposition and cross bonding.

Technical feature

Along each section, a standing voltage is induced. In ideal cross-bonding systems the three section lengths are equal, so that no residual voltage occurs and thus no screen current flows.

MC types are supplied with GPH® mechanical connectors.

The outer sheath is restored with heavy wall adhesive lined tubing or in case of limited space with a wrap-around sleeve with or without Al foil.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Screen
-
Technology
-

Dimensional characteristics

Dimensional characteristics

Conductor cross-section, range
400 ... 630 mm²
Diameter over insulation, range
32 ... 52 mm
Length
1200 mm
Maximum outer diameter
66.0 mm
Minimum outer diameter
44.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
18 / 30 (36) kV

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close