Nexans H07RN-F TITANEX 7G1.5
Nexans H07RN-F TITANEX 7G1.5
TITANEX
The TITANEX® flexible rubber cable range offers exceptional performances and is designed to release you from all your constraints. Robust yet flexible, TITANEX® is easy to use and withstands the toughest of conditions, such as hard-wearing situations, extreme temperatures and most chemicals
Lue lisää- Artikkelinro : 20070698-901-05
- STK-nro : 0410191
- EAN : 3427680015846
Kuvaus
Kuvaus
Standardit
-
Product2014/68/EU; EN 50525-2-21; HD 516; IEC 60245-4 type 66; NF C32-102-4
-
KansainvälinenEU Directive 2011/65/EU (RoHS)
Advantages
TITANEX (H07RN-F) on EPR-eristeinen ja kumivaippainen liitäntäkaapeli, jossa on pyöreät monisäikeiset kuparijohtimet. Kaapeli on SS 424 02 35-4 -standardin mukainen, öljyn- ja rasvankestävä sekä taipuisa, joka kestää suuria lämpötilavaihteluja, kosteutta ja pakkasta. TITANEX on tarkoitettu väliaikaiseen sisä- ja ulkoasennukseen. Sopii liitettäväksi koneisiin ja muihin materiaaleihin, jotka edellyttävät taipuisaa kaapelia. Johtimen resistanssi on IEC 60228 luokan 5 mukainen. Johtojen väritunnistus on SS 424 17 20:n mukainen. Vaippa on täytetty ja siihen on merkitty tyyppi/valmistaja/vuosi+kuukausi/metrimäärä. TITANEX täyttää CPR class E.
Installation
TITANEX H07RN-F cables can be laid in cable trays, on shelves, inside ducts or fixed to walls, outside with or without protection. They can also be immersed with additionnal mechanical protection. Additionnaly, they can also be intalled outdoors without protection (UV resistance).
Minimum bending radius
- Dynamic : 6 to 8 x outer diameter of the cable.
- Static : 3 x outer diameter of the cable if OD< or = 12mm ; 4x if OD > 12mm.
Laying cable conductors
When pulling the cable, all conductors must be equally stressed. Th tensils force must never exceed 15N/mm2 of total cross-sections.
Th maximum tensile force should never exceed 1000N in total, although the above rule may lead to higher values for large cross-sections.
Marking
TITANEX 90°C n (x or G) s NEXANS CE «har» USE H07RN-F - factory n° Made in France Y Eca n°DoP
Metric marking
Marking every metre, so that only the required length is unwound.
TITANEX MADE TO SURVIVE
Additional informations Nexans TITANEX
Core identification
(In accordance with european harmonization HD308 S2)
1x: black
2x: brown - blue
3x: brown - black - grey (brown - black - blue if the conductor cross-section is 1.5 or 2.5mm²)
3G: brown - blue - green/yellow
4x: brown - black - grey - blue
4G: brown - black - grey - green/yellow
5x: black cores with printed numbers
5G: blue - brown - black - grey - green/yellow
7 cores and above : black cores with printed numbers
Current rating capacities
The data are indicated for continuous duty operation and apply to:
- Maximum conductor temperature = 90 °C
- Nominal frequencies = 50 or 60 Hz
- One cable in free air (on perforated trays)
- Ambient temperature = 30 °C
Data recording from IEC 60364-5-52 or NF C 15-100
Voltage drop
The data are based on Cos ø = 0.8
Minimum bending radius
- Static use: 3 x cable outer diameter
- Dynamic use: 6 to 8 x outer cable diameter.
Nexans Titanex, Made to survive
NEXANS TITANEX FEATURES
Ominaisuudet
Ominaisuudet
Rakenteelliset ominaisuudet
Rakenteelliset ominaisuudet
Mittatiedot
Mittatiedot
Sähköiset ominaisuudet
Sähköiset ominaisuudet
Mekaaniset ominaisuudet
Mekaaniset ominaisuudet
Käsittelytiedot
Käsittelytiedot
Resurssit
Resurssit
Dokumentaatio
Myynti- & toimitustiedot
TITANEX-kaapelin toimituspituudet ovat 50 - 500 m. Kelaan on merkitty valmistaja, kaapelityyppi ja pituus.
Suorituskykyilmoitus
- Suorituskyvyn ilmoitus nro : 1000236-FRBH
- Varmennuspäivä : 15.3.2022
- AVCP (suorituskyvyn arviointi ja jatkuva valvonta) : System 3
- Ilmoitettu elin : NB 1812
- Suorituskyky : Eca